T/EX Series High Frequency Online UPS

Short Description:


Product Detail

Product Tags

Application:

T/EX Series 6KVA~20KVA High frequency online UPS is specially designed for servers,data-center critical network devices,sensitive electronic equipment,telecom,bank,hospital,bureau,traffic,public security,Army and so on.

FEATURES:

l Large Blue Ground LCD digital display shows Detailed Real-Time UPS Status and parameters.

l Output Voltage,Frequency parameter and bypass function can be set via the display.

l Advanced MCU microprocessor control technology and DSP technology,ensure long life reliability.

l Wide input voltage range,Zero transfer time.

l True online double conversion technology.

l N+X Parallel Rseundancy.

l Excellent Protection against over voltage,over load,over current,over charge and so on.

l Input L and N lines reverse wiring detection,Auto start when AC back.

l DC start function,Input PFC revise function.

l Humanization bypass output,can be adjustable.

l Smart RS232 communication with monitoring software.

l Intelligent slot available for AS-400 Dry contact and SNMP card Remote control.

l Available to work with generators.

l Lightning,surge,short circuit,Network/fax/modem surge protection.

SPECIFICATIONS:

Slide to the left for full table
LCD MODEL EX6K EX10K EX6KL EX10KL EX3110K EX3110KL EX3115KL EX3120KL
LED MODEL T6K T10K T6KL T10KL T3110K T3110KL T3115KL T3120KL
CAPACITY VA/W 6KVA4.2KW 10KVA7KW 6KVA4.2KW 10KVA7KW 10KVA7KW 10KVA7KW 15KVA10.5KW 20KVA14KW

INPUT

Nominal Voltage

220/230/240VAC

380VAC

Voltage Range

176-276VAC

304-478VAC

Frequency Range

50Hz:46~54Hz;60Hz:56~64Hz

Phase

Single phase with Ground

Three phase (4 Wires+Ground)

Power Factor

>=0.97

>=0.95

OUTPUT

Voltage

220/230/240*(1±1%)VAC

Frequency

50/60Hz(Adjustable)

50Hz AC Mode:Follow AC Mode(AC Range 46~54Hz);

Battery Mode:50Hz(1±0.2%)

60Hz AC Mode:Follow AC Mode(AC Range 56~64Hz);

Battery Mode:60Hz(1±0.2%)

Wave Form

Pure Sine Wave

Power Factor

0.7/0.8

Harmonic Distortion

=<2% THD (Linear Load),=<6% THD (Non-Linear Load)

Overload Capacity

105%-130% for 10 min,130% for 1 min

Current Crest Ratio

3:1

Connections

Terminal block

Efficiency

To AC Mode

88%

85%

To Battery Mode

87%

Battery

Type

Sealed free maintenance lead acid battery

Nominal DC voltage Built in batteries 12v7.2ah*20pcs

240VDC

12v7.2ah

240VDC

Quantity 20pcs 20pcs Depends on requested back-up time 20pcs

Depends on requested back-up time

Back-up Time (Full load)

>=7 minutes

>=5 minutes

Depends on the capacity of external battery bank

>=5 minutes

5minutes

Depends on the capacityof external battery bank
Recharge Time

7 hours to 90%

Depends on the capacity of external battery bank 7 hours to 90% Depends on the capacity of external battery bank
Charge current(MAX)

2.0A

4.2A or 8A

2.0A

4.2A or 8A

Charge voltage

274Vdc±1%V

Bypass

Automatic Transfer

On overload and UPS failure

Before UPS Power-on

Default “ON” user adjustable to “YES”

Transfer Time

Zero

Indicators LED/LCD Display

UPS status,I/P & O/P voltage&frequency,Battery voltage,Battery capacity,Loading,Fault code

Audible Alarm

Bypass,On battery mode,Battery low,Overload,Fault

Acoustic noise At 1 meter distance

<55dB

<60dB

Communications

Intelligent RS232 serial port Windows 98/NT/2000/XP/2003,Linux,Sun Solaris,IBM Aix,Compaq True64,SGI IRIX,FreeBSD,HP-UX,and MAC
SNMP(Optional) Power management from SNMP manager and web browser
USB(Optional) Windows family software and Mac OS
Environmental Operating Temperature

0~40℃

Operating Humidity

20~90%(Non Condensing)

Weight Net weight

84

93

35

38

88.5

39.5

58

58

UPS Dimension L*W*H(mm)

570*260*717

*LED/LCD display panel optional

*Product specifications are subject to change without further notice.