Leave Your Message
您的浏览器版本不支持canvas
APQ Series Modify Sine Wave Inverter & Charger
Low Frequency Modify Sine Wave Inverter & Charger

APQ Series Modify Sine Wave Inverter & Charger

Short Description:

● Low Frequency design, Modified sine wave output

● off mode charging

● Full automatic and silent operation

● Built-in 20Amp super charger for up to 100Ah battery

● Three-steps intelligent charging control to recharging time

● informative LED indicator and alarms

● Different AC outlet configurations available: NEMA,  Schuko, French ,India

● Small scale and cost effective for home appliances and office equipment

    product detail

    The APQ modified sine wave inverter/charger shall utilize line-interactive topology. It consists of an auto transformer, battery charger, battery, inverter, transfer switches and all associated controls, monitoring and major protection devices. It shall denote the hardware and firmware associated to provide high quality AC power for sensitive electronic and other critical loads. In the event of utility abnormalities (sags and swells), the AC output power shall be corrected by means of boost (sag correction) or buck (swell correction) compensation taps. Operation of the compensation taps shall be seamless and automatically maintain the proper output voltage for the connected critical equipment. The compensation taps shall be designed for indefinite operation at full rated load to their voltage limits, without discharging the battery.

    ● Low Frequency design, Modified sine wave output

    ● off mode charging

    ● Full automatic and silent operation

    ● Built-in 20Amp super charger for up to 100Ah battery

    ● Three-steps intelligent charging control to recharging time

    ● informative LED indicator and alarms

    ● Different AC outlet configurations available: NEMA,  Schuko, French ,India

    ● Small scale and cost effective for home appliances and office equipment

    Slide to the left for full table
    APQ Specification
    Inverter output Model 600W 1000W
    Continuous Output Power 600W 1000W
    Surge Rating(20s) 1800W 3000W
    Putput Waveform Modified Sine Wave/Same as input(Bypass mode)
    Nominal Efficiency 80%(Peak)
    Line Mode Efficiency >95%
    Power Factor 0.9-1.0
    Nominal Output Voltage rms 110V/120V/220V/230V/240VAC
    Output Voltage regulation ±10%rms
    Output Frequency 50Hz ± 0.3Hz/60Hz ± 0.3Hz
    Short Circuit Protection Yes(1s after fault)
    Typical transfer Time 10ms(Max)
    DC Input Nominal Input Voltage 12V 24V
    Minimum Start Voltage 10V 20V
    Low Battery Alarm 10.5V 21V
    Low Battery Trip 10V 20V
    High Voltage Alarm 16V 32V
    Low Battery voltage recover 13V 26V
    Charge Input voltage Range 75/90-150VAC 115/148-290VAC
    Output Voltage ±10%rms
    Charger Breaker Rating 10A 20A
    Max Charge Rate 30A/15A
    Battery Initial Voltage for Start 0-15.7V for 12V(*2 for 24V)
    Over Charge Protection Shutdown 15.7V for 12V(*2 for 24V)
    Charger curve (4 stage constant current)Battery  types 4 step digital controlled progressive charge
    Bypass & Protection Input Voltage Waveform Sine wave(Grid or Generator)
    Nominal Voltage 110VAC/120VAC 230VAC
    Low Voltage Trip 75/90V±4% 115/148V±4%
    Low Voltage re engage 85V/100V±4% 125V/158V±4%
    High Voltage Trip 150V±4% 290V±4%
    High Voltage re engage 140V±4% 280V±4%
    Max Input AC Voltage 170VAC 300VAC
    Nominal Input Frequency 50Hz or 60Hz (Auto detect)
    Low Freq Trip 45±0.3Hz for 50Hz,55±0.3Hz for 60Hz
    Low Freq re engage 47±0.3Hz for 50Hz,57±0.3Hz for 60Hz
    High Freq Trip 55±0.3Hz for 50Hz,65±0.3Hz for 60Hz
    High Freq re engage 54±0.3Hz for 50Hz,64±0.3Hz for 60Hz
    Overload protection(SMPS load) Circuit breaker& Software Protection
    Output Short circuit protection Circuit breaker& Software Protection
    Bypass breaker rating 10A 20A
    MechanicalSpecifications
      Mounting Wall mount
      Inverter Dimensions(L*W*H) 285×145×145mm
      Inverter Weight 12KG 16KG
      Shipping Dimensions(L*W*H) 385×245×245mm
      Shipping Weight 14KG 18KG
      Display Status LEDs
      Standard 1 Year